Accessories

Various accessories to be used with other Ventmatika products.

All conform to EU, UK and CIS laws and regulations.

EKR 6.1 - controller for single or two-phase heaters
EKR 6.1 - single-phase or two-phase electric heater regulator

Designed to control single-phase and two-phase electric heaters without integrated control.

A temperature sensor is built into the heater, which allows it to be controlled based on the room temperature. As standard, the control is based on the supply air sensor.*

Adjustable temperature setting limits – 0..30°C or 0..60°C.

The operating mode is determined when installing the regulator, using the switches inside.

Night function – the ability to reduce the temperature setting to 10°C at night, with an external timer.

Controlled power:

  • 1x230V – 3.2kW
  • 2x400V – 6.4kW
  • Maximum current: 16A

*Sensor should be ordered separately.

Accessories

TJ-K10K - supply air temperature sensor
TJ-K10K - supply air sensor

Duct mounted temperature sensor.

TJ-K10K - supply air sensor

Duct mounted temperature sensor.

EKR 15 - controller for three-phase electric heaters up to 240kW
EKR 15 - three-phase electric heater controller up to 240kW

Controller for three-phase electric heaters with power up to 240kW. Controls by supply or extract air temperature sensors* or an external 0..10VDC control signal.

Extra steps activated by sequential or binary mode, depending on heater power.

Models and maximum outputs:

ModelTriac stepExtra stepsVoltageMax. output
EKR 15.115kW1x5A/230V3x400V30kW
EKR 15.1P15kW4x5A/230V3x400V240kW
*Sensors should be ordered separately.

Accessories

TJ-K10K - supply air temperature sensor
TJ-K10K - supply air sensor

Duct mounted temperature sensor.

TJ-K10K - supply air sensor

Duct mounted temperature sensor.

EKR 30 - controller for three-phase electric heaters up to 480kW
EKR 30 - heater regulator

Controller for three-phase electric heaters with power up to 480kW. Controls by supply or extract air temperature sensors* or an external 0..10VDC control signal.

Extra steps activated by sequential or binary mode, depending on heater power.

Models and maximum outputs:

ModelTriac stepExtra stepsVoltageMax. output
EKR 3030kW1x5A/230V3x400V60kW
EKR 30P30kW4x5A/230V3x400V480kW
*Sensors should be ordered separately.

Accessories

TJ-K10K - supply air temperature sensor
TJ-K10K - supply air sensor

Duct mounted temperature sensor.

TJ-K10K - supply air sensor

Duct mounted temperature sensor.

TR5K / TR5KNTC10 - setpoint controller for NI type electric heaters or EKR heaters controllers
TR5KNTC10 regulator

TR5K – external wired remote setpoint for NI type heaters. The heater is working based on supply air temperature sensor.

TR5KNTC10 – external wired remote setpoint for NI type heaters with internal temperature sensor. When connected, the heater is working according to the internal sensor, and the supply air temperature sensor limits supply air temperature – +15°C…+40°C.